Baseline Design Part II - Estimating the Heating Load

3/2/2013

0 Comments

 
This post will show a rough estimate of the total annual heating load not taking any solar gain into account.   This will provide a baseline estimate of how much energy (and $$) can be saved annually.

Assumptions
As a quick summary, the assumptions are listed below:
 - Total Heating Degree Days        3905
 - Ceiling R-Value                            38
 - Wall R-Value (2x6)                       24
 - Low E windows R-Value                 3.57   (U = .28)
 - ACH50                                          7   

A preliminary floor plan is shown below.   Although we're still making a lot of revisions, it's close enough to make some estimates of heating load.
Picture
Picture

The front of the house faces north and the back faces south.

The footprint is roughly 2175 square feet with a full basement.

There's about 960 square feet of windows.  I know this is way too much for an energy efficient design but the views are worth it.  We will have to compensate by making improvements in other areas.

First floor walls are about 2263 square feet.   The basement walls are about 2480 square feet and the total volume is about 42,750 cubic feet.


Heat Loss Through Insulation
This is a rough estimate so I'm taking some shortcuts.
I'm going to treat the basement walls the same as the first floor, although the basement is not primary living space and generally will be left at a much cooler temperature.  On the other hand, I'm also ignoring any heat loss through the basement floor.

The general formula is to divide the area by the R value to get a heat loss per degree per hour and then multiply by the total number of Heating Degree Days times 24 hours in a day.  
 
    Heating Load in BTU per Year = (Area / R) x HDD x 24

    - Ceiling                 ( 2175 / R38 ) x 93,720    =      5,364,236 BTU per year
    - 1st floor walls       ( 2263 / R24 ) x 93,720    =      8,837,015 
    - basement walls    ( 2480 / R24 ) x 93,720    =      9,684,400
    - Windows             (  960 / R3.57) x 93,720   =     25,139,453


Heat Loss Due to Air Infiltration
To estimate heat loss from air infiltration, we have to calculate the cubic feet of air lost per hour and then calculate the amount of heat lost based on heating degree days.

The minimum code allows 7 air changes per hour using a pressure test at 50 pascals.  Since the house has a total voume of 42,750 cubic feet (counting the basement) then code would allow a loss of 299,250 cubic feet of air per hour or 4988 cubic feet per minute (CFM).  That is a LOT of air!

To estimate the amount of air that would be lost in normal (i.e. natural)  conditions we divide by a fudge factor called the Energy Climate Factor.  For the North Central climate zone the Energy Climate Factor is 20... I don't know how they came up with this, I merely looked it up. 

     ACH(normal) = ACH(50) / N where N is defined to be 20

     ACH(normal) = 7 / 20 = 0.35  air changes per hour 
 
This indicates that under normal conditions the house will vent 14,963 cubic feet of air per hour or 269 CFM.  This is still a LOT of air!

To calculate total BTUs per hour you multiply by the Specific Heat (SH) for air.  Specific Heat (SH) is the term that describes how many BTUs are contained in one cubic foot of material (per degree).   Air isn't very dense and doesn't carry much heat.  Air has a Specific Heat of .018 BTU per cubic foot per degree.

So the heat loss per hour per degree equals the voulume of air times the SH.

     Heat Loss per hour per degree = (ACH50 x SH=0.018) / N=20

     14,963 x .018 = 269 BTUs  per hour per degree

To get the annual heat loss we multiply the hourly heat loss by the Heating Degree Days (HDD) times 24 hours in a day.
     269 x 93720 = 25,241,139 BTU per year


Summary
 The following table summarizes the annual heat loss for the baseline design. 
  

    - R38 Ceiling                       5,364,237                7.2%
    - R24 1st floor walls             8,837,015              11.9%
    - R24 basement walls          9,684,400              13%
    - R 3.57 Windows              25,139,453              33.8%
    - Air Infiltration (ACH = 7)   25,241,139              34%
    - TOTAL                           74,266,244
  
Though it seems counter-intuitive, the R38 ceiling is the least concern since it is only responsible for 7.2% of the heat loss.  The walls have a much larger surface area and loose more heat than the ceiling.  The biggest opportunity for improvement is air infiltration.

In the next post, I'll calculate the energy cost for a few different heating systems
   
  

0 Comments



Leave a Reply.

    Archives

    April 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    May 2020
    January 2019
    December 2018
    February 2018
    January 2018
    December 2017
    September 2017
    July 2017
    June 2017
    March 2017
    November 2016
    October 2016
    September 2016
    August 2016
    July 2016
    May 2016
    April 2016
    March 2016
    February 2016
    January 2016
    December 2015
    October 2015
    September 2015
    August 2015
    July 2015
    June 2015
    April 2015
    November 2014
    October 2014
    September 2014
    August 2014
    July 2014
    June 2014
    May 2014
    April 2014
    March 2014
    February 2014
    January 2014
    December 2013
    November 2013
    October 2013
    September 2013
    August 2013
    July 2013
    June 2013
    March 2013
    February 2013
    January 2013


    Categories

    All
    2nd Amendment
    3D Printers
    AI
    ANTIFA
    AOC
    Apocoloptimist
    Armor
    Artemis
    Asteroids
    Baseline
    Boogeymen Of Doom
    Canning Cooking
    Canning-cooking
    Climate Hysteria
    Clown World
    Constitution
    Construction
    Cutting Cable
    Deck
    Depopulation
    Don't Panic
    Driveway
    Electrical
    Electric Vehicles
    Elitism
    Elon Musk
    Energy
    Euthanasia
    Fatphobia
    Fearsome Fallout
    Fertilizer
    Firewood
    Flamethrowers
    Front Porch
    Fun Stuff
    Fun With 80/20
    Fun With LEDs
    Future Food
    Gestapo
    Globalism
    Health Care
    Home Automation
    Home Automation
    Ikea
    Insect Farming
    Insulation
    Kamala
    Karma
    Kitchen
    Ministry Of Truth
    Multi Splits
    Multi-splits
    Open Borders
    Pandemic
    Passive Solar
    Photovoltaics
    Plumbing
    Psychology Of Fear
    Random Thoughts
    Rational Prepper
    Scarcity
    Science Projects
    Solar Power
    Spiraling Crime
    Stairs And Railings
    Starlink
    Star Trek
    Steel
    Sunspot Cycles
    Superior Walls
    Suspended Slab
    Sustaining Liberty
    Temperature Sensors
    The Changing World Order
    The End Of Private Property
    The Great Reset
    Ukraine
    Unrivaled
    Urban Exodus
    Victory Gardens
    Waffle House
    WEF
    Widllife
    Winning
    Woodland Gardens


    Follow Me on Pinterest

    RSS Feed